Specification | Details |
---|---|
Rating in KVA: | 2 KVA Online |
Technology: | IGBT-PWM |
Input Voltage: | AC 110V – 300V 50Hz |
Nominal Input Current: | 7.73A |
IN Rush Current Limit: | 8 IRMS |
DC Bus Voltage: | 72 VDC |
Efficiency: | 92% |
Power Factor Load Supported: | 0.8 |
Overload Limit: | 50% Overload for 3 Sec |
THDi: | <9% Maximum @ 100% Load 230V Input |
Input Power Factor: | 0.99 Full Load @ 230V Input |
Battery Backup Bank: | With Battery |
Input Frequency Range: | 45-55Hz/54-66Hz |
Input Protection: | Breaker |
OVCD: | Withstand 440Vac |
Nominal Output Voltage: | 200VAC/208VAC/220VAC/230VAC/240VAC |
Output Power (VA): | 2000VA |
Output Voltage: | AC 230V +/-1% 50Hz |
Output Power (W): | 1600 |
Output Power Factor: | 0.8 |
Output Waveform: | Pure Sine Wave |
Output Transient Recovery: | 100ms |
Output Harmonic Distortion (THD%): | <3% THD, Linear Load @ Line Mode <3% THD, Linear Load @ Battery Mode, 12V Battery <7% THD, Non-Linear Load @ Line Mode <7% THD, Non-Linear Load @ Battery Mode, 12V Battery |
Output Frequency in Inverter Mode: | 45-55Hz/54-66Hz |
Output Frequency Slew Rate: | 1Hz/s |
Transfer Time Inverter Mode to Battery Mode: | 0ms |
Transfer Time Inverter Mode to Bypass Mode: | 4ms |
Line Mode Efficiency @ Full Load with Battery Full Charged: | >90% |
Battery Mode Efficiency @ Full Load 12VDC/Battery: | >86% |
Battery Backup Provided with Online UPS: | Yes, with Battery |
Backup Time: | 30 Minutes |
No of Battery Use: | 6 |
Battery Make: | eWit |
Accessories: | Rack for Battery |
Additional Features: | Pure Sinewave AC Output |
Design: | Floor Standing |
Protection: | IP21 |
Working Temperature: | -10°C to +65°C |
Casing: | Plastic |
Installation: | Provided |
Country of Origin: | India |